§ 11-113. Same—Amendments.  


Latest version.
  • Paragraph 2.5.4 of the safety code adopted by this article is amended by deleting the table contained therein and, in lieu thereof, inserting the following table:

    Minimum Distance of Storage and Handling
    Facilities From Permanently Occupied
    Structures and Places of Public Assembly

    Quantity
    (gallons)
    Distance
    (feet)
    0 to 250   125
    251 to 500   250
    501 to 2,000   500
    2,001 to 20,000 1,000
    20,001 to 32,000 1,500
    Over 32,000 2,000

     

    In no case shall a facility be less than 50 feet from a public roadway.

    To site a single container of over 32,000 gallons in capacity shall require permission of the city council.

(Ord. No. 927, § 3, 2-28-84)